Technical data of DH professional industrial dryers

Show all x DH 15 x DH 30 x DH 60 x DH 60 H x DH 160 x DH 160 stainless steel shop x DH 310
DH 15
DH 30
DH 60
DH 160
DH 160 stainless steel shop
DH 310

Technical data Equipment, features and...

2,017.05 € incl. VAT Show net price (VAT not included)

3,088.05 € incl. VAT Show net price (VAT not included)

4,617.20 € incl. VAT Show net price (VAT not included)

Price on request

12,488.75 € incl. VAT Show net price (VAT not included)

16,005.50 € incl. VAT Show net price (VAT not included)

22,253.00 € incl. VAT Show net price (VAT not included)

Technical data
General information
Article number 1.125.000.111 1.125.000.116 1.125.000.121 1.125.000.123 1.125.000.161 1.125.000.162 1.125.000.175
Dehumidification performance
At 20 °C / 60 % RH [l/24h] 11 20 38 85 85
At 30 °C / 80 % RH [l/24h] 22 46 90 245 245 500
Max. [l/24h] 70
Air flow rate
Level Max. 225 635 1,165 1,000 2,200 2,200 4,600
Operating range
Min. temperature [°C] 5 5 5 5 1.5 1.5 1.5
Max. temperature [°C] 40 40 40 32 42 42 42
Min. humidity [%RH] 30 30 30 30 30
Min. humidity [%r.F.] 50 30
Max. humidity [%RH] 90 90 90 95 95
Max. humidity [%r.F.] 90 95
Electrical values
Mains connection 220 - 240 V, 50 Hz 220 - 240 V, 50 Hz 220 - 240 V, 50 Hz 220 - 240 V, 50 Hz 400 V, 50 Hz 400 V, 50 Hz 400 V, 50 Hz
Nominal current consumption [A] 3.7 4.2 7.5 19 9.5 9.5 9.5
Power input [kW] 0.657 0.922 1.523 4.3 3.5 3.5 6.9
Required current starting phase [A] 18 15.8 30 50 50 75
Recommended fusing [A] 10 16 16 16 16 16 25
Electric connection
Connection plug CEE 7/7 CEE 7/7 CEE 7/7 CEE 7/7 CEE 16 A CEE 16 A CEE 32 A
Heat emission
kW 0.9 1.9 3.5 9 9 18
Coefficient of performance (COP) 1.6 2.5 2.9 2.9 2.9 3
Heat recovery optional optional
Max. heat emission to water [kW] 1.4 2.8
Compressor
refrigerant R-407C R-407C R-407C R-407C R-407C R-407C R-407C
Amount of refrigerant [g] 480 500 800 800 2,250 2,250 3,200
GWP factor 1,774 1,774 1,774 1,773.85 1,774 1,774 1,774
CO2 equivalent [t] 0.851 0.887 1.419 1.42 3.99 3.99 5.68
Pressure suction side [MPa] 0.7 0.7 0.8 0.8 1.8 1.8 1.8
Pressure outlet side [MPa] 2.5 2.5 2.7 2.7 2.8 2.8 2.8
Sound values
Distance 3 m [dB(A)] 49 52 54 59 59 60
Functions and features
Automatic fault diagnosis system
Connection for external condensate drain
Dimensions
Length (packaging excluded) [mm] 365 255 255 356 560 560 690
Width (packaging excluded) [mm] 840 790 1,253 1,331 700 700 1,080
Height (packaging excluded) [mm] 330 651 651 880 1,355 1,355 1,715
Weight
(packaging excluded) [kg] 37 47 70 50 150 150 230
Equipment, features and functions
Automatic defrost system
Hot gas
Hygrostat
Internal
External
Condensate drain
Hose connection possible
Hose included in the scope of delivery
Condensate pump
Recommended hose size [mm] 10 10 10 10 16 mm 16 mm 16
Condensate pump
Available
Integrated condensate pump
Housing design
Steel coated
Metal
Room air filter
Readily accessible
Cleanable
Mobility
Forklift
Feet

 standard equipment

 optionally available

 not available